Risbabh EM94-Z-V3-M-D, Panel Mount DC kWh Meter, Class 0.5, 50-150mV Shunt input, 201-1000VDC, 2 Alarm/Pulse Outputs, RS485 & USB Comms, Single Line LCD Display,10-60VAC/DC Aux Supply, Internal Logging
- 2 Pulse/Alarm Outputs
- 50-150mV Shunt Input, and nominal voltage 201-1000VDC
- RS 485 communication up to 57,600 bit/s
- USB Port
- 8MB Internal Storage
- DC Measurement Only
The meter is intended for measuring, analysing and monitoring DC Power. The meter records TRMS value according to the principle of fast sampling of voltage and current signals. A built-in microprocessor calculates measurands (voltage, current,, energy, power.) from the measured signals.
Features :
- 96 x 96mm Panel Mount
-
Accuracy class 0.5
- Simple Menu
- RS 485 communication up to 57,600 bit/s
- USB Comms
- 8MB Internal Logger
- 10-60VAC/DC power supply
Specification
Rishabh Part Number | EM94-Z-V1-M-D |
Functions | kWh Meter, Energy Meter |
Supply Voltage | 10-60VAC/DC |
Nominal Measurement Range | 201-1000VDC |
Maximum Measurement Range | 60-300VDC |
Display | Single Line LCD |
Pulse/Relay Output | 2 |
Accuracy | Class 0.5 (Energy) |
USB | YES |
Real Time Clock | 1min/month (30ppm) |
Isolation | 3.5kV |
RS485 Modbus RTU | YES 57,600bps |
Weight | 450g |
Certification | EN 61010-1 Installation Category III |
Factory Pack Qty | 1 |
Environment |
IP54
|
Safety |
Protection Class II |
Enclosure Material | Mablex with fire protection to UL94-V-O. Self extinguishing |
EnclosureSize | 96 x 96mm x 83.5mm (72mm behind panel)
|
Terminals | Rising Cage 4mm² (12 AWG) cable max |
Humidity | < 75% Non Condensing |
Operating Temperature | -20 →+70 °C |
Datasheet
- Product Datasheet
Software
- Software User Manual
- Software Download Link
Application Notes
1)Reading Data from Registers -> Download file
2)Maximum Memory Size -> Read below
Max Available Memory Locations in 8MB Size = 273030
Actual parameter stored in Each log (Memory locations used) = Date +time+Number of parameter selected by user
Considering your example for 2 parameters:
Number of parameter selected by user = 2 (kwh & kVA)
Actual parameter stored in Each log = 1(Date) +1(time)+ 2 (Parameters) = 4 (memory locations used per log)
Maximum log that can be stored = Max Memory Location/Actual parameter stored in Each log =273030/4= 68257
Timelog Interval setting = 15 minutes
Log in one day = (60 /Timelog Interval setting) * 24 =(60/15)*24 = 96 Logs
Max Days = Maximum log that can be stored / log in one day = 68257 / 96 = 711 days = 1 Year & 11 Months = 23 Months.