INCLUDES:
• (1) Fluke 1587 FC Insulation Multimeter
• (1) Fluke i400 AC Current Clamp
• (1) Crocodile Clips
• (1) Test Probes
• (1) Test leads
• (1) Remote probe
• (1) Type K Thermocouple
• (1) Instruction CD
• (1) Hard Carry Case
FEATURES:
• With the Fluke 1587 FC, perform insulation tests, plus a wide-range of DMM tasks with confidence and ease
• Use the Fluke i400 with your Fluke 1587 FC to accurately measure AC current without breaking the circuit
• Pl/DAR measurements with TrendIt graphs
• Memory storage through Fluke Connect Measurements app
• Temperature Compensation through Fluke Connect Measurements app
• VFD low-pass filter for accurate motor drive measurements
• Insulation test voltages 50 V, 100 V, 250 V, 500 V, 1000 V
• Insulation test voltages 500 V, 1000 V
• Insulation test: 0.01 M? to 2.0 G?
• Insulation test: 0.1 M? to 600 M?
• Auto-discharge of capacitive voltage
SPECIFICATIONS:
• AC Voltage Measurement Range: 600.0 Mv, 6.000 V, 60.00 V, 600.0 V, 1000 V
• AC Voltage Measurement Resolution (0.1 Mv) Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts): ±(1% + 3), Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts): ±(1% + 3), Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts): ±(1% + 3), Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts): ±(1% + 3), Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts): ±(2% + 3)
• AC Voltage Measurement Resolution (0.1 Mv) Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts): ±(2% + 3), Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts): ±(2% + 3), Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts): ±(2% + 3), Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts): ±(2% + 3)¹, Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts) ±(2% + 3)¹
• Low-Pass Filter Voltage Range: 600.0 mV, 6.000 V, 60.00 V, 600.0 V, 1000 V
• Low-Pass Filter Voltage Resolution (0.1 mV) Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts): ±(1% + 3), Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts): ±(1% + 3), Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts): ±(1% + 3), Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts): ±(1% + 3), Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts): ±(2% + 3)
• Low-Pass Filter Voltage Resolution (0.1 mV) Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts): +(2% + 3), -(6% – 3), Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts): ±(1% + 3), Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts): ±(1% + 3), Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts): ±(1% + 3), Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts): ±(2% + 3)
• Low-Pass Filter Voltage Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts): +(2% + 3), -(6% – 3), Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts): +(2% + 3), -(6% – 3), Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts): +(2% + 3), -(6% – 3), Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts): +(2% + 3), -(6% – 3), Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts): +(2% + 3), -(6% – 3)
• DC Voltage Measurement Range: 6.000 V dc, 60.00 V dc, 600.0 V dc, 1000 V dc
• DC Voltage Measurement Resolution: 0.001 V, 0.01 V, 0.1 V, 1 V
• DC Voltage Measurement Accuracy ±(% of Rdg + Counts): ±(0.09% + 2), ±(0.09% + 2), ±(0.09% + 2), ±(0.09% + 2)
• Input Impedance: 10 M? (Nominal), <100 pF
• Normal Mode Rejection Ratio: >60 dB @ 50 Hz or 60 Hz
• Common Mode Rejection Ratio: >120 dB @ dc, 50 Hz or 60 Hz (1 k Unbalance)
• DC Millivolts Measurement Range: 600.0 mVdc
• DC Millivolts Measurement Resolution: 0.1 mV
• DC Millivolts Measurement Accuracy ±(% of Rdg + Counts): ±(0.1% + 1)
• DC and AC Current Range (AC 45 Hz to 1000 Hz): 400 mA
• DC and AC Current Resolution: 0.1 mA
• DC and AC Current Accuracy ±(% of Rdg+Counts): ±(1.5% + 2)¹
• DC and AC Current Burden Voltage (Typical): 2 mV/mA
• DC and AC Current Range: 60 mA
• DC and AC Current Resolution: 0.01 mA
• DC and AC Current Accuracy ±(% of Rdg+Counts): ±(1.5% + 2)¹
• DC and AC Current Burden Voltage (Typical)L 2 mV/mA